Summary
Successful exploitation of these vulnerabilities could allow for an attacker to perform a man-in-the-middle (MitM) attack, cause a factory reset, wipe credentials, or retrieve sensitive information.The following versions of Tycon Systems TPDIN-Monitor-WEB3 are affected:
- TPDIN-Monitor-WEB3 <=2.2.9 (CVE-2026-77847, CVE-2026-82712, CVE-2026-82684)
CVSS
Vendor
Equipment
Vulnerabilities
v3 8.8
Tycon Systems
Tycon Systems TPDIN-Monitor-WEB3
Use of Hard-coded Credentials, Cross-Site Request Forgery (CSRF), Missing Authorization
Background
- Critical Infrastructure Sectors: Critical Manufacturing, Energy
- Countries/Areas Deployed: Worldwide
- Company Headquarters Location: United States
Vulnerabilities
Expand All +
CVE-2026-77847
Tycon Systems TPDIN-Monitor-WEB3 versions 2.2.9 and prior are vulnerable to a Use of Hard-coded Credential vulnerability. This could allow an attacker to intercept sensitive information or credentials.
View CVE Details
Affected Products
Tycon Systems TPDIN-Monitor-WEB3
Vendor:Tycon Systems
Product Version:Tycon Systems TPDIN-Monitor-WEB3: <=2.2.9
Product Status:known_affected
Remediations
Vendor fixTycon Systems has released TPDIN-Monitor-WEB3 Firmware v2.4.2.
MitigationUnits already running v2.4.2, for subsequent updates (signed container):
https://firm.tyconsystems.com/tpdin-monitor-web3-v2/TPDIN-MONITOR-WEB3-V2_v2.4.2.tfw
MitigationAll units currently in the field, including the v2.2.9 covered by this report (legacy Intel HEX):
https://firm.tyconsystems.com/tpdin-monitor-web3-v2/TPDIN-MONITOR-WEB3-V2_v2.4.2T.hex
MitigationA unit running v2.2.9 installs the .hex build directly and arrives at v2.4.2 in a single step; no intermediate version is required. The signed .tfw container cannot be read by a v2.2.9 updater, which accepts only Intel HEX, so the .hex artifact is the one every deployed unit needs.
MitigationFor more information, contact Tycon Systems:
https://www.tyconsystems.com/contact
Relevant CWE: CWE-798 Use of Hard-coded CredentialsMetrics
CVSS Version
Base Score
Base Severity
Vector String
3.1
6.5
MEDIUM
CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N
4.0
7.1
HIGH
CVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N
CVE-2026-82712
Tycon Systems TPDIN-Monitor-WEB3 versions 2.2.9 and prior are vulnerable to a Cross-Site Request Forgery vulnerability. This could allow an attacker to perform state changing operations on the device.
View CVE Details
Affected Products
Tycon Systems TPDIN-Monitor-WEB3
Vendor:Tycon Systems
Product Version:Tycon Systems TPDIN-Monitor-WEB3: <=2.2.9
Product Status:known_affected
Remediations
Vendor fixTycon Systems has released TPDIN-Monitor-WEB3 Firmware v2.4.2.
MitigationUnits already running v2.4.2, for subsequent updates (signed container):
https://firm.tyconsystems.com/tpdin-monitor-web3-v2/TPDIN-MONITOR-WEB3-V2_v2.4.2.tfw
MitigationAll units currently in the field, including the v2.2.9 covered by this report (legacy Intel HEX):
https://firm.tyconsystems.com/tpdin-monitor-web3-v2/TPDIN-MONITOR-WEB3-V2_v2.4.2T.hex
MitigationA unit running v2.2.9 installs the .hex build directly and arrives at v2.4.2 in a single step; no intermediate version is required. The signed .tfw container cannot be read by a v2.2.9 updater, which accepts only Intel HEX, so the .hex artifact is the one every deployed unit needs.
MitigationFor more information, contact Tycon Systems:
https://www.tyconsystems.com/contact
Relevant CWE: CWE-352 Cross-Site Request Forgery (CSRF)Metrics
CVSS Version
Base Score
Base Severity
Vector String
3.1
8.8
HIGH
CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H
4.0
8.6
HIGH
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:A/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N
CVE-2026-82684
Tycon Systems TPDIN-Monitor-WEB3 versions 2.2.9 and prior are vulnerable to a Missing Authorization vulnerability. This could allow an attacker to extract system credentials, configurations, or flash contents.
View CVE Details
Affected Products
Tycon Systems TPDIN-Monitor-WEB3
Vendor:Tycon Systems
Product Version:Tycon Systems TPDIN-Monitor-WEB3: <=2.2.9
Product Status:known_affected
Remediations
Vendor fixTycon Systems has released TPDIN-Monitor-WEB3 Firmware v2.4.2.
MitigationUnits already running v2.4.2, for subsequent updates (signed container):
https://firm.tyconsystems.com/tpdin-monitor-web3-v2/TPDIN-MONITOR-WEB3-V2_v2.4.2.tfw
MitigationAll units currently in the field, including the v2.2.9 covered by this report (legacy Intel HEX):
https://firm.tyconsystems.com/tpdin-monitor-web3-v2/TPDIN-MONITOR-WEB3-V2_v2.4.2T.hex
MitigationA unit running v2.2.9 installs the .hex build directly and arrives at v2.4.2 in a single step; no intermediate version is required. The signed .tfw container cannot be read by a v2.2.9 updater, which accepts only Intel HEX, so the .hex artifact is the one every deployed unit needs.
MitigationFor more information, contact Tycon Systems:
https://www.tyconsystems.com/contact
Relevant CWE: CWE-862 Missing AuthorizationMetrics
CVSS Version
Base Score
Base Severity
Vector String
3.1
8.1
HIGH
CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:N
4.0
8.6
HIGH
CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:N/SC:N/SI:N/SA:N
Acknowledgments
- Abdiwelli Guled reported these vulnerabilities to CISA.
Legal Notice and Terms of Use
This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy).
Recommended Practices
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities.
Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
Locate control system networks and remote devices behind firewalls and isolating them from business networks.
When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
CISA also recommends users take the following measures to protect themselves from social engineering attacks:
Do not click web links or open attachments in unsolicited email messages.
Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.
Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.
No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.
Revision History
- Initial Release Date: 2026-09-03
Date
Revision
Summary
2026-09-03
1
Initial Publication